Free Call Australia : 1 800 834 991

Related Products

High Voltage AC Dielectric Test Sets 3 kV - 300 kV Upto 40 kVA

PONOVO FT3000 DC Converting Station Test Equipment 
  • Precisely and automatically complete power filter amplitude frequency
  • Automatically measure power filter by parameters of reactor, capacitor and resistor
  • Quickly and accurately test all parameters of power filter by this single device

Product Details

PONOVO FT3000 DC Converting Station Test Equipment

Precisely and automatically complete power filter amplitude frequency and phase frequency characteristic measurement. Automatically measure power filter by parameters of reactor, capacitor and resistor. Compensate and measure capacitor group unbalanced current 0.01 mA—10 mA
Features
• Quickly and accurately test all parameters of power filter by this single device
• High precision: field test accuracy can reach 5 ‰.
• High efficiency: compared to the traditional testing methods it saves much time and labor force.
• Safe and reliable: using high-frequency low-level signal does not generate dangerous high voltage. Thus no safety issue is in the picture in the field.
Main Specifications
Signal source technical parameters
Max output voltage 60V RMS
Max output ccurrent 5A
Output frequency 5Hz—3000Hz
Frequency control step 0.1 Hz
Measurement system technical parameters
Voltage
Accuracyq 0.5%
Frequency 5Hz—3000Hz
Amplitude 0.2V—60V
Current
Accuracy 0.5%
Frequency 5Hz—3000Hz
Amplitude 0.01 A—10 A
Impedance measurement accuracy 0.5%
Impedance measurement range 1O—6KO
Phase measurement accuracy 1°
Inductance measurement accuracy 0.5%
Inductance measurement range 2mH—10H
Capacitance measurement accuracy 0.5%
Capacitance measurement range 0.05uF—500uF
Unbalance current measurement accuracy 0.5%
Frequency output 100Hz—3000Hz
Amplitude output 0.01 mA—10 mA
Other
Operation Off-line operation/External PC operation
Communication Port USB/100M Ethernet
Self Protection Overload/Overheat
Report 1000 Reports
LCD 8.4" TFT
Dimension 364 mm×200 mm×475mm (W×H×D)
Weight 11.8kg

MIRUS Drive Tamers Transformers Designed to replace standard drive isolation transformers, the Drive Tamerâ„¢ is built to not only withstand the harsh harmonic environment produced by Varia...
MIRUS Harmony-3E Isolation Transformers and Auto Transformers HARMONYâ„¢ SERIES isolation transformers and autotransformers combine very low zero sequence impedance outputs with phase shift...
MIRUS Onics Harmonic Mitigating Power Center The Onics HMPC is an outstanding power distribution unit ideal for the raised floor environment. It incorporates MIRUS' patented and proven Ha...
MIRUS Combined Neutral Current Eliminator (CNCE) A patented phase shifting autotransformer with a low zero sequence impedance at its output. When connected in series on a 3-phase, 4-wire ...
MIRUS Neutral Current Eliminator (NCE) A 3-phase, low zero sequence impedance autotransformer, which when connected near to and in parallel with the harmonic generating non-linear loads (...